I. Fire Extinguishing Principle
1. Temperature control: When the ambient temperature rises to a nominal value, the valve on the fire extinguishing device opens automatically and releases ultra-fine dry powder fire extinguishing agent.
2. Thermal initiation: In a specific environment, when the fire extinguishing device needs to be started quickly, the fire signal is quickly transmitted to the fire extinguishing device through the heat sensitive line, and the fire extinguishing device starts to release ultra-fine dry powder fire extinguishing agent.
3. Electronic control: The electronic control fire extinguishing device can connect with all fire alarm controllers, output feedback signals when spraying, detect composite fire signals by detectors and send them to fire alarm controllers. The controller confirms and outputs command signals (command signals are divided into passive switch signals and active energy signals). The command signals are activated by repeaters. The dynamic fire power supply opens the valve to the fire extinguishing device and releases the ultra-fine dry powder fire extinguishing agent to extinguish the fire.
 
II. Main Advantages
1. Effectiveness of fire extinguishing
It can realize passive spontaneous start-up, extinguish the fire in the early stage of ignition, realize early suppression and reduce losses.
2. Simple system and low cost
Ultra-fine dry powder automatic fire extinguishing device does not need to set up special storage bottles, occupies a small area, does not need power supply and complex electronic control equipment and pipelines, does not need special smoke and temperature sensors, avoids the possibility of misoperation, system construction is simple, high reliability, saves building area, and greatly reduces the cost of construction.
3. Small dosage of fire extinguishing agent and low cost of fire extinguishing
The traditional fixed gas fire extinguishing system takes the room with large enclosed space as the protective area, while the ultra-fine dry powder automatic fire extinguishing device only determines the amount of fire extinguishing agent according to the area or volume calculated by the protective object, which greatly reduces the amount of fire extinguishing agent and reduces the cost of a fire extinguishing.
 
III. Existing Types and Specifications
1. Types:
The main fire extinguishing devices are ultra-fine dry powder fire extinguishing devices for vehicles (small cars, large passenger cars or freight cars, train fire extinguishing devices), suspended ultra-fine dry powder automatic fire extinguishing devices (non-storage suspension, storage suspension), ultra-fine dry powder fire extinguishing bombs, etc.
2. Main Specifications
(1) Pressure storage type: temperature sensing start-up:
The main specifications are 4kg, 5kg, 8kg and 10kg.
(2) Non-storage type: solenoid valve, heat sensitive line start-up:
The main specifications are 3kg, 5kg, 8kg and 10kg.
 
IV. MAIN PARAMETERS
1. Pressure-stored ultra-fine dry powder:
 
Specification type  FZX-ACT4/1.2-JXJA  FZX-ACT5/1.2-JXJA  FZX-ACT8/1.2-JXJA  FZX-ACT10/1.2-JXJA
Outline size(mm)      φ255×384.5      φ255×404.5         φ300×455       φ350×440
Filling weight(kg)           4               5                    8                   10
Protection space(m3)        30               38                   61                  76
Starting parameter            temperature starting  68℃         electric starting  DC24v(0.5-1.5A)
Spraying time(s)                                           ≤5
Using temperature(℃)                                     -10-+50
Service life                                                5years
Fire extinguishing type                                    A,B,C fire and electric fire
Execution standard for fire extinguishing agents                 GA602-2013
 
2. Non-Pressure Storage Ultrafine Dry Powder:
Specification type  FFX-ACT3-JXJA    FFX-ACT5-JXJA    FFX-ACT8-JXJA    FFX-ACT10/1.2-JXJA
Outline size(mm)      φ205×380      φ270×377        φ270×458           φ350×460
Filling weight(kg)           3              5                    8                   10
Protection space(m3)        23               38                   61                  76
Elctric starting parameter                                   DC24v700mA
Spraying time(s)                                           ≤5
Using temperature(℃)                                     -40-+50
Service life                                                5years
Fire extinguishing type                                    A,B,C fire and electric fire
Installation height requirements(m)                           3.5-8.5
 
V.Application fields (sites)
It is suitable for archives, car warehouses, kitchens, offices, construction sites, warehouses, oil depots, insurance rooms, archives, telecommunications base stations, gas stations, substations and other places.