Perfluorohexanone fire extinguishing device
 
I. Fire Extinguishing Principle
The main way to extinguish the fire is to remove most of the heat in the fire site, that is, after the release of perfluorohexanone fire extinguisher, it forms a gaseous mixture with carrier gas N2, which is very easy to absorb or consume a large amount of heat, so as to quickly extinguish the flame temperature and achieve efficient fire extinguishing.
 
II. Main Advantages
1. Good environmental protection performance: green environmental protection gas;
2. High efficiency of fire extinguishing: low concentration of fire extinguishing can quickly extinguish fire;
3. Safety of use: No cases of low toxicity were found.
4. Good electrical insulation performance: no damage to insulators of ordinary wires and cables;
5. Quick cooling effect: fire extinguisher has unique cooling effect after spraying.
6. Fire extinguishing without residue: It volatilizes quickly after use and will not cause damage to precision instruments and antique paintings.
7. Storage and transportation at atmospheric pressure is safe: liquid at normal temperature, can be transported according to ordinary goods, easy to fill, transport and storage;
Electrical fire, solid surface fire, liquid fire and gas fire which can cut off gas source before extinguishing fire. 8. Extinguishable
 
III. Existing Categories and Specifications
Customizable according to customer requirements.
 
IV. MAIN PARAMETERS
1. Melting point: - 108 ℃;
2. Boiling point: 49 ℃
3. Density: 1,6 g/cm 3;
4. Viscosity of liquid: (0 /25), Mpa s: 0.56/0.39;
5. Insulation performance (110Kv): 3.8mA (standard leakage current < 10mA);
6. Non-volatile residues:<0.01;
7. Design concentration: 3.5-5.5;
8. Fire extinguishing and spraying time: general protective area is less than 10s, communication room and computer room are less than 8s;
9. Rated boosting pressure:
10. Unit filling rate in fire extinguishing agent storage containers:
The first-stage pressurized storage container should not be greater than 1480 (Kg/m3); the second-stage pressurized storage container should not be greater than 1440 (Kg/m3);
11. Water content of nitrogen should be less than 0.006%.
12. Design temperature of fire extinguishing system: 20 ℃;
13. Design of fire extinguishing concentration in special places:
(1) The fire extinguishing design concentration is 10% in protective areas such as books, archives, bills and cultural relics databases.
(2) Oil-immersed transformer room. The design concentration of fire extinguishing is 9% in the power distribution room with oil switch and the self-contained generator room.
(3) The fire extinguishing design concentration is 8% in protective areas such as communication room and computer room.
 
Ⅴ. Application Areas (Places)
It is widely used in regional or local fire extinguishing systems and portable fire extinguishers, especially in electronic control center, computer room, distribution room, distribution cabinet, wind power room, energy storage power station, advanced precision instruments, museums, data processing center, ship control engine room, lithium batteries for new energy vehicles, Metro station, etc. Fire protection in large supermarkets, dense public places, etc.
 
Not applicable to material fires in the following places:
1. Fire of oxidants such as nitrocellulose, sodium nitrate or chemicals containing oxidants;
2. Fires of active metals such as potassium, magnesium, sodium, titanium, zirconium and uranium;
3. Metal hydride fires such as potassium hydride and sodium hydride;.
4. Fire of chemical substances such as hydrogen peroxide and diamine which can decompose by themselves;
5. Deep fire of combustible solids.
 
 
 
 
 
 
 